Non-Cycling Refrigerated Dryer

The RGD Series refrigerated air dryers offer the perfect balance between technology and simplicity to dry compressed air systems to a stable SO 8573-1 Air Quality, Class 4 to 5 pressure dew point. The smooth bore, copper tube-on-tube heat exchangers make for an innovative, efficient system. These dryers are available with an inlet flow of 10 - 1200 SCFM.


RGD 15-50 SCFM

  • Smooth bore, copper tube-on-tube heat exchangers
  • Centrifugal separator efficiently captures condensate
  • Static condenser design provides trouble free, quiet operation
  • Electronic drain valve

RGD 75-1200 SCFM

  • Stainless steel, cross flow heat exchangers optimize heat transfer and service life
  • Compact design saves floor space
  • Stainless steel inlet/outlet connections to prevent corrosion
  • Timed electric condensate drain
  • Integral demister/separator

Model

Inlet Flow 

Pressure Drop 

Voltage 

Dimensions

Refrigerant 

In/Out Connections

Power Consumption

Weight 

 

 

 

 

 

Height

Width

Depth

 

 

 

 

 

SCFM

NM³/H

PSI

 

IN

MM

IN

MM

IN

MM

 

NPT

kW

lbs

RGDA7A1

7

11.9

3.5

115/1/60

18

445

15

366

17

425

R 513a

3/8" MNPT

0.15

47

RGDA11A1

11

18.7

6.0

115/1/60

18

445

15

366

17

425

R 513a

3/8" MNPT

0.16

47

RGDA15A1

15

25.5

8.5

115/1/60

18

445

15

366

17

425

R 513a

3/8" MNPT

0.16

47

RGDA25A1

25

42.5

0.5

115/1/60

21

534

18

455

21

514

R 513a

1/2" FNPT

0.27

63

RGDA32A1

32

54.4

0.6

115/1/60

21

534

18

455

21

514

R 513a

1/2" FNPT

0.27

63

RGDA42A1

42

71.4

1.0

115/1/60

21

534

18

455

21

514

R 513a

1/2" FNPT

0.51

74

RGDA50A1

50

85.0

1.3

115/1/60

21

534

18

455

21

514

R 513a

1/2" FNPT

0.52

74

RGD75A1

75

127

2.5

115/1/60

24

609

15

381

33

838

R 134a

1"

0.52

123

RGD100A1

100

170

3.3

115/1/60

24

609

15

381

33

838

R 134a

1"

0.65

129

RGD125A1

125

212

3.7

115/1/60

24

609

15

381

33

838

R 134a

1"

0.68

135

RGD150A1

150

255

3.0

115/1/60

21

533

13

330

30

762

R 134a

1"

1.11

161

RGD200A4

200

340

2.6

460/3/60

30

762

20

493

37

932

R 134a

1 1/2"

1.42

183

RGD250A4

250

424

2.8

460/3/60

30

762

20

493

37

932

R 134a

1 1/2"

1.98

211

RGD300A4

300

509

3.1

460/3/60

32

812

20

493

44

1112

R 134a

1 1/2"

2.05

219

RGD400A4

400

680

2.5

460/3/60

30

762

21

787

38

965

R 134a

2"

2.5

232

RGD500A4

500

849

3.0

460/3/60

32

812

22

558

48

1218

R 407c

2"

3.18

328

RGD600A4

600

1019

3.7

460/3/60

32

812

22

558

50

1270

R 407c

2"

3.8

353

RGD600W4

600

1019

3.7

460/3/60

32

812

22

558

50

1270

R 407c

2"

3.8

353

RGD800A4

800

1359

2.8

460/3/60

59

1450

30

762

42

1067

R 407c

3" FLG

5.4

687

RGD800W4

800

1359

2.8

460/3/60

59

1450

30

762

42

1067

R 407c

3" FLG

5.4

687

RGD1000A4

1000

1699

2.9

460/3/60

64

1626

29

737

45

1143

R 407c

4" FLG

6.6

786

RGD1000W4

1000

1699

2.9

460/3/60

64

1626

29

737

45

1143

R 407c

4" FLG

6.6

786

RGD1200A4

1200

2038

3.9

460/3/60

64

1626

29

737

45

1143

R 407c

4" FLG

8.66

810

RGD1200W4

1200

2038

3.9

460/3/60

64

1626

29

737

45

1143

R 407c

4" FLG

8.66

810

Maximum Inlet Air Temperature: 120°F (49°C) Maximum Operating Pressure: 250 psig (Models RGD25–50), 232 psig (Models RGD75–500).
Above conditions tested at 100°F inlet air temperature, 100% saturated inlet air, 100 psig operating pressure and 100°F ambient air temperature.

Operating Conditions

Model

Max Inlet
Air Pressure

Min Inlet
Air Pressure

Max Inlet
Air Temperature

Min Inlet
Air Temperature

Max Ambient
Air Temperature

Min Ambient
Air Temperature

SCFM

PSIG

BARG

PSIG

BARG

°F

°C

°F

°C

°F

°C

°F

°C

5–10 to 50

250

17

30

2

120

49

40

4

110

43

45

7

75–500

232

16

10

1

120

49

40

4

110

43

45

7

600–1200

232

16

43

3

120

49

45

7

110

43

34

1

Capacity Correction Factors

To adjust the dryer capacity for non-standard conditions, use the Capacity Correction Factors (multipliers) from the tables below.

Sizing Example
What is the capacity of a RGD100 at 100°F inlet air temperature, 150 psig working pressure and 110°F ambient air temperature?

Answer
100 scfm (rated flow from RGD specifications table) × 1.08 (correction factor for inlet air temperature, table 1) × 0.94 (correction factor for ambient air temperature, table 2) = 102 scfm

TABLE 1

Inlet Air Pressure

Inlet Air Temperature

PSIG

BARG

90°F/32°C

100°F/38°C

110°F/43°C

120°F/49°C

80

5.6

1.19

0.95

0.77

0.63

100

6.9

1.25

1

0.82

0.68

125

8.6

1.3

1.05

0.86

0.72

150

10.3

1.34

1.08

0.9

0.75

175

12.1

1.37

1.11

0.92

0.78

200

13.8

1.39

1.14

0.95

0.8

250

17.2

1.43

1.17

0.98

0.83

TABLE 2

Ambient Air Temperature

80°F/27°C

90°F/32°C

100°F/38°C

110°F/43°C

Multiplier

1.12

1.06

1

0.94