DGH Series Heatless desiccant dryers open up a world of customizable performance opportunities with four standard ISO quality class levels of pressure dew points to choose from. Don't settle for less than the ability to satisfy all of your requirements for clean, dry compressed air. A carefully engineered desiccant dryer design provides a reliable method to remove moisture as a water vapor. With the option to add coalescing filters, solid particles, liquid water droplets, liquid oil and oil vapors can be removed from the compressed air system in a reliable manner.


Sizing Information (Table -1)

Model

scfm

Inlet Flow
@ 100 psig,
(7 bar)
Dimensions – inchesConnectionsWeight
HeightWidthDepthinchesLBS.

DGH40

404632321" NPT365

DGH60

606132321" NPT445

DGH90

907832321" NPT575

DGH115

1155444381" NPT685

DGH165

1655444381" NPT685

DGH260

2607248382" NPT1010

DGH370

3706355382" NPT1215

DGH450

4507155382" NPT1350

DGH590

59010152482" NPT1473

DGH750

75010454482" NPT2134

DGH930

93010959562" NPT2414

DGH1130

113011263563" ANSI Fig.2875

DGH1350

135011765563" ANSI Fig.3722

DGH1550

155011571564" ANSI Fig.4167

DGH2100

210011679564" ANSI Fig.4417

DGH3000

300012278654" ANSI Fig.9010

DGH4100

410012293856" ANSI Fig.9900

DGH5400

5400122102866" ANSI Fig.12000

NOTE : BSP connections and DN Flg available. Dimensions and weights are for reference only. Request certified drawings for construction purposes.

Sizing Information (Table -2)

Operating Pressurepsig60708090100110120130140150175200225250
bar4.24.95.66.37.07.78.49.19.810.512.314.115.817.6
Multiplier 0.650.740.830.911.001.041.081.121.161.201.291.371.451.52
NOTE : To determine inlet flow at pressures other than 100 psig (7 kgf/cm²) multiply inlet flow at 100 psig from Table 1 by the multiplier that corresponds to your operating pressure from Table 2.

Operating Parameters

  • Maximum Working Pressure 150 psig standard.Higher pressures are available
  • Minimum Operating Pressure for 150 psig models are 60 psig
  • Minimum Operating Pressure for 250 psig models are 120 psig
  • Maximum inlet or ambient air temperature 120° F (49° C)
  • Pressure drop at rated flow is less than 5 psi
  • Standard voltages: Controllers automatically identify and adapt the controller: Basic: 100–120V/1ph/5–60Hz;Energy Savings Controller: 100–240V/1ph/50–60Hz & 12–24 VDC
  • NEMA 4 Standard Feature with Standard and Energy Savings Controllers

NOTES

  • Inlet Flow : Inlet flow are established in accordance with CAGI Standard ADF-200: Dual Stage Regenerative Desiccant Compressed Air Dryers-Methods for Testing and Rating. Conditions for rating dryers are: inlet pressure of 100 psig, inlet temperature saturated at 100° F.
  • Average purge flow rate is the amount of purge air used during the regeneration portion of the purge cycle (purge/repressurization valve open) plus the volume of air used to repressurize the tower after the purge/repressurization valve closes averaged over the cycle time. 
  • At 100 psig, the average purge rate is: 14.4% (13.7% for regeneration + 0.7% for repressurization) of rated inlet flow for dryers operating on a 10 minute cycle; 15.5% (13.7% for regeneration + 1.8% for repressurization) for dryers on a 4 minute cycle.
  • Outlet Flow: To determine flow of air available at outlet of dryer, subtract purge flow from inlet flow.